UAT 459 UAS, Internet of Things and Smart Warehouse Systems

Worksheet 6 Draft the architecture and check the requirements of a mock cold room

Lab 4 hAssesses CLO4

Objective

Draw the four-layer IoT architecture of a real space, compute the alert time budget and availability, set pre-alarm limits from an uncertainty budget and compute battery life

Equipment and materials

  • Computer with Python and the example code at /downloads/uat-459/
  • Two wireless temperature sensors
  • Reference thermometer with a calibration certificate
  • Refrigerator or mock cold room prepared by the instructor
  • Multimeter or low-current meter (if available)

Safety

  • Desk and computer work, no flying
  • In the cold room wear warm clothing, stay no more than 15 minutes at a time, check the door opens from inside and keep a partner outside
  • Do not open lithium battery packs or short battery terminals while measuring current
  • Do not change settings of refrigerators or rooms that hold real samples or chemicals

Steps

  1. Choose a real space and draw the four-layer architecture of Figure 1, answering the three questions (function, data lost or delayed, owner) for every box
  2. Use Examples 1 and 2 to compute the alert time budget and availability, then vary the two most uncertain values
  3. Install two wireless sensors next to the reference thermometer, record together for at least 30 minutes and compute the mean difference
  4. Build an uncertainty budget as in Example 3 and set pre-alarm limits
  5. Measure currents or take them from datasheets, then compute battery life as in Example 4 for the group's chosen interval

Record of results

Table 1 Architecture boxes and the three questions
Device or boxLayer (device, network, service support, application)FunctionIf it fails: data lost or only delayedOwner
Table 2 Alert time budget and availability with sensitivity analysis
CaseRecording interval (s)Alert time (min)Margin (min)AvailabilityDowntime (h/year)
Table 3 Sensor comparison, uncertainty budget, pre-alarm limits and battery life
ItemSensor 1Sensor 2UnitSource or note

Questions

  1. Which part of the group's alert time budget takes the longest? Would a faster network help much, and why?

  2. Why is the availability of the whole alarm path lower than its weakest part, and besides a second gateway, what else would the group propose?

  3. How does the mean difference between the group's sensors and the reference thermometer compare with the expanded uncertainty U and the ±0.5 °C requirement? Is the sensor acceptable?

  4. Why does a BLE sensor's battery life hardly change when the interval is lengthened, while a LoRaWAN sensor's changes a lot? Which radio did the group choose for its space?

Check before you hand in

What to hand in

  • Architecture diagram with the three-question table
  • Time budget and availability tables with sensitivity analysis
  • Uncertainty budget and pre-alarm limits
  • Battery life table and radio recommendation

CLO4 Explain the IoT architecture of smart warehouses and select sensors, edge devices, gateways and communication protocols that meet the requirements of the operation. (CLOs are a web-team draft; the course owner sets the final ones.)

Instructors: answers and teaching notes for this worksheet are in the teaching pack