UAT 459 UAS, Internet of Things and Smart Warehouse Systems
Worksheet 6 Draft the architecture and check the requirements of a mock cold room
Objective
Draw the four-layer IoT architecture of a real space, compute the alert time budget and availability, set pre-alarm limits from an uncertainty budget and compute battery life
Equipment and materials
- Computer with Python and the example code at /downloads/uat-459/
- Two wireless temperature sensors
- Reference thermometer with a calibration certificate
- Refrigerator or mock cold room prepared by the instructor
- Multimeter or low-current meter (if available)
Safety
- Desk and computer work, no flying
- In the cold room wear warm clothing, stay no more than 15 minutes at a time, check the door opens from inside and keep a partner outside
- Do not open lithium battery packs or short battery terminals while measuring current
- Do not change settings of refrigerators or rooms that hold real samples or chemicals
Steps
- Choose a real space and draw the four-layer architecture of Figure 1, answering the three questions (function, data lost or delayed, owner) for every box
- Use Examples 1 and 2 to compute the alert time budget and availability, then vary the two most uncertain values
- Install two wireless sensors next to the reference thermometer, record together for at least 30 minutes and compute the mean difference
- Build an uncertainty budget as in Example 3 and set pre-alarm limits
- Measure currents or take them from datasheets, then compute battery life as in Example 4 for the group's chosen interval
Record of results
| Device or box | Layer (device, network, service support, application) | Function | If it fails: data lost or only delayed | Owner |
|---|---|---|---|---|
| Case | Recording interval (s) | Alert time (min) | Margin (min) | Availability | Downtime (h/year) |
|---|---|---|---|---|---|
| Item | Sensor 1 | Sensor 2 | Unit | Source or note |
|---|---|---|---|---|
Questions
Which part of the group's alert time budget takes the longest? Would a faster network help much, and why?
Why is the availability of the whole alarm path lower than its weakest part, and besides a second gateway, what else would the group propose?
How does the mean difference between the group's sensors and the reference thermometer compare with the expanded uncertainty U and the ±0.5 °C requirement? Is the sensor acceptable?
Why does a BLE sensor's battery life hardly change when the interval is lengthened, while a LoRaWAN sensor's changes a lot? Which radio did the group choose for its space?
Check before you hand in
What to hand in
- Architecture diagram with the three-question table
- Time budget and availability tables with sensitivity analysis
- Uncertainty budget and pre-alarm limits
- Battery life table and radio recommendation