UAT 202 Fundamentals of Automation Technology

Worksheet 2 Testing sensors and actuators on the training rig

Lab 6 hAssesses CLO1

Objective

Test presence sensors, wire PNP/NPN correctly, measure a 4–20 mA loop and drive a pneumatic actuator

Equipment and materials

  • PLC training rig with 24 VDC supply
  • Inductive, capacitive and photoelectric sensors
  • 4–20 mA calibrator or multimeter
  • Solenoid valve, pneumatic cylinder and compressor
  • Metal, plastic and battery-box test pieces

Safety

  • Power off before connecting or removing any wire; the lecturer checks before power-up
  • Wear safety glasses with compressed air and vent pressure before removing hoses
  • Keep hands and cables clear of the cylinder stroke

Steps

  1. Test the three sensors on the three test pieces and record detection distances
  2. Read sensor and input-module labels; identify PNP/NPN and sinking/sourcing
  3. Power off, wire to the diagram, have the lecturer check, then power up and test
  4. Measure the loop at 4, 12 and 20 mA and check with Example 1
  5. Disconnect one signal wire, observe the reading and check the program flags a fault
  6. Drive the solenoid valve, time the cylinder stroke and state whether it is single or double acting

Record of results

Table 1 Detection distance of each sensor and test piece
Sensor (type, and PNP or NPN from the label)Metal piece (mm)Plastic piece (mm)Battery box (mm)PLC input used (sinking or sourcing)
Table 2 The 4–20 mA loop of the 0–100 °C temperature transmitter
Current (mA)Temperature by hand (°C)Value shown by the programProgram status message
Table 3 Pneumatic cylinder stroke times
RunExtend time (s)Retract time (s)Single or double acting, and the evidence seen

Questions

  1. From Table 1, which sensors detected the plastic battery box and which did not? Explain by working principle, then choose a sensor for three station jobs: the metal gripper arm, the battery box and the drone on the landing pad.

  2. When the signal wire was disconnected, what current did you read and what did the program show? Why does this signal start at 4 mA rather than 0 mA, and what should the station do when it sees such a reading?

  3. If a PNP sensor were wired to a sourcing input module, what would happen when it detects an object? Explain using the direction of current.

  4. The charging cabinet's 230 V AC fan draws 6 A. Under the team's 1.25 margin, may the Omron MK-S relay, rated 10 A resistive and 7 A inductive, switch it? Why?

Check before you hand in

What to hand in

  • Detection-range table
  • Checked wiring diagram
  • mA versus scaled-value table and broken-wire result
  • Cylinder stroke-time record

CLO1 Explain automation components: sensors, controllers and actuators. (CLOs are a web-team draft; the course owner sets the final ones.)

Instructors: answers and teaching notes for this worksheet are in the teaching pack