UAT 453 UAS for Infrastructure, Energy and Utility Inspection
Worksheet 13 Anomalies in thermal and rust images
Objective
Find thermal anomalies by group comparison, compute rust grades from images and assess automatic-detection errors
Equipment and materials
- Thermal camera or drone with one
- Several identical units, e.g. fan motors or breakers
- Rusty steel plate
- Python and module 13 example code
Safety
- Image electrical panels from a safe distance with the building electrician opening them; never touch live parts
- Beware of hot surfaces and rotating motor parts
- Ground work; flying not required, and if flown follow CAAT conditions in visual line of sight
Steps
- Take thermal images of identical equipment under load
- Read temperatures and find anomalies with Example 1
- Try the mean instead of the median and explain the difference
- Photograph the rusty plate and segment with a simple colour threshold
- Compute the grade with Example 2
- Check the segmentation by eye and record over-counts and misses
Record of results
| Item | Temperature (°C) | ΔT vs median (°C) | ΔT vs mean (°C) | Level (normal, monitor, replace) |
|---|---|---|---|---|
| Image or panel | Total pixels | Rust pixels | Percent rusted | D610 grade |
|---|---|---|---|---|
| Area | Over-counted or missed | What it really is (stain, shadow, weld, rust) | How to fix |
|---|---|---|---|
Questions
How far apart were your median and mean, and which item looked more normal than it is with the mean?
Why image under load while running, and what wrong conclusion would you draw from stopped equipment?
How trustworthy is your rust grade after checking over-counted and missed areas?
Why should software screen and a qualified inspector decide? Give an example from your results.
Check before you hand in
What to hand in
- Temperature table and anomalies
- Median versus mean comparison
- Segmented image and rust grade
- Over-count and miss record