UAT 362 Unmanned Aircraft Systems Technology for Industrial, Energy and Infrastructure Applications
Worksheet 3 Reading thermal patterns on a solar array
Objective
Capture thermal images of a solar array under correct conditions, classify module- and string-level anomalies and confirm with other data
Equipment and materials
- Drone or thermal camera kit with a colour camera
- Irradiance meter, thermometer and anemometer
- String layout and inverter current data from the system operator
- Python and the module 3 example code
- Lab notebook
Safety
- Fly within CAAT conditions in visual line of sight and coordinate with the operator before entering
- Do not touch modules, cables or DC equipment; work under the operator's supervision
- Beware of sun heat; drink water and rest in shade
Steps
- Take thermal images on a sunny day, recording irradiance, air temperature and wind
- Tabulate module temperatures by the real string layout
- Use Example 1 to classify module- and string-level anomalies with criteria set before viewing results
- Confirm findings with colour images and inverter current data
- Write a findings list with module positions, possible causes and follow-up checks
Record of results
| Time | Irradiance (W/m²) | Air temperature (°C) | Wind speed (m/s) | Thermal and colour image numbers |
|---|---|---|---|---|
| String | String median (°C) | Difference from array median (K) | Modules above string median by the criterion (K) | Inverter current (A) | Anomaly level |
|---|---|---|---|---|---|
| Position (string-module) | Thermal pattern | Possible cause | Confirmation (colour image, current) | Follow-up check |
|---|---|---|---|---|
Questions
In Table 2, which string is warm as a whole and which module is hot on its own? What should the repair team check first in each case?
If each module were compared only with the whole-array median, using the same 5 K criterion, how would your results change?
Why must the 2 K and 5 K criteria (or your group's) be set before viewing the results? What happens to the report if they are set afterwards?
Does the inverter current data confirm or contradict what the thermal images show? If they disagree, what will your group do next?
How could the conditions in Table 1 (sunlight, wind, time) make your images misleading, and why does real work need the criteria from the actual IEC TS 62446-3?
Check before you hand in
What to hand in
- Thermal images with conditions
- Module temperature table
- Anomaly classification
- Findings list