Power lines and electrical connections
UAT 453 UAS for Infrastructure, Energy and Utility Inspection
Lesson
By the end of this module you will be able to
- Explain why electrical connections overheat and the principle of comparing with similar components
- Rate hot spots by severity using the NETA ΔT criteria
- Estimate full-load ΔT from a low-load measurement and explain its limits
- Define suitable conditions for thermal imaging of electrical systems
Why this matters
A loose, dirty or corroded connection has higher resistance than normal. When current flows, heating concentrates there. Left alone, the connection gets hotter until the material degrades and breaks, causing an outage. Drone thermal imaging finds these spots without switching off power, but deciding which must be repaired immediately needs clear criteria and an understanding of electrical load.
Comparing with similar components
Temperatures read from a drone carry errors from emissivity, distance and wind, so absolute values are not very reliable. The widely used approach is to compare with similar components under similar load, such as the same type of connection on another phase of the same tower. The difference cancels errors that affect all phases alike.
Table 100.18 of ANSI/NETA ATS gives guidance by between similar components:
| between similar components | Meaning and action |
|---|---|
| 1–3 °C | Possible deficiency; warrants investigation |
| 4–15 °C | Probable deficiency; repair as time permits |
| Over 15 °C | Major discrepancy; repair immediately |
The same table warns that temperature criteria vary by equipment type, and that heating relates to the square of current, so load at the time of measurement matters greatly.
Example 1 Rating four connections
readings = { # connector: (measured °C, other phase at equal load °C)
"tower 17 clamp phase A": (41.0, 38.5),
"tower 17 clamp phase B": (38.5, 38.5),
"tower 23 jumper phase C": (47.0, 38.0),
"tower 31 clamp phase A": (61.0, 39.0),
}
def action(dt):
if dt > 15:
return "major discrepancy, repair immediately"
if dt >= 4:
return "probable deficiency, repair as time permits"
if dt >= 1:
return "possible deficiency, investigate"
return "no action"
for name, (t, ref) in readings.items():
print(f"{name:<24} dT {t - ref:4.1f} C -> {action(t - ref)}")
tower 17 clamp phase A dT 2.5 C -> possible deficiency, investigate
tower 17 clamp phase B dT 0.0 C -> no action
tower 23 jumper phase C dT 9.0 C -> probable deficiency, repair as time permits
tower 31 clamp phase A dT 22.0 C -> major discrepancy, repair immediately
The connection at tower 31 is 22 °C hotter than the other phase, a major discrepancy needing immediate repair. Tower 23 differs by 9 °C, to be repaired as planned. Tower 17 phase A differs by 2.5 °C and should be re-checked or imaged from another angle, because such a small difference may come from camera angle, sunlight or slight emissivity differences.
The effect of electrical load
Because heating scales with , a faulty connection may not look very hot when measured at low load. A simple estimate of full-load ΔT multiplies by the square of the current ratio
Example 2 Measured at 40% load
DT_MEASURED, LOAD_NOW, LOAD_FULL = 6.0, 0.40, 1.00 # measured ΔT, and load fraction now versus full
dt_full = DT_MEASURED * (LOAD_FULL / LOAD_NOW) ** 2 # heating scales with current squared (approximation)
print(f"measured {DT_MEASURED} C at {LOAD_NOW:.0%} load -> about {dt_full:.1f} C at full load")
measured 6.0 C at 40% load -> about 37.5 C at full load
A ΔT of 6 °C at 40% load appears to be in the “repair as time permits” group, but at full load it could reach about 37.5 °C, far above the major threshold. This simple estimate ignores cooling that changes with temperature and wind; use it as a warning to prioritise, not as an exact reported figure. Better practice is to schedule imaging at high load, using load data from the control centre.
Suitable conditions for electrical thermography
- High enough load, per the owner’s data, recording the load at every measurement
- Light wind, because wind carries heat away and lowers ΔT
- Avoid strong direct sun and reflections: shiny metal reflects radiation from the sky and sun, so early morning or after sunset often gives easier interpretation
- Enough distance and pixels: connections must span several thermal pixels, or their temperature is averaged with the background and reads low
- Paired zoom RGB images to identify which part the hot spot is
Module lab
Lab: thermal images of an electrical panel
- Under the supervision of the university’s electrical staff, take thermal images of a control panel or connections that can be reached safely (a handheld or ground-based thermal camera is fine)
- Read the temperature of the same type of connection on every phase, compute ΔT and rate it with the code in Example 1
- Obtain the load at the time of measurement and estimate full-load ΔT with the code in Example 2
- Record wind, light and time, and write how these conditions might bias the results
Common mistakes
Watch out
- Judging by absolute temperatures from the drone instead of comparing with similar components
- Not recording load at measurement, so ΔT cannot be interpreted
- Imaging in strong wind or direct sun, then concluding there are no hot spots
- Imaging from so far that connections span only a few pixels, so temperatures are averaged low
- Reporting estimated full-load ΔT as an exact figure
Summary
- Faulty connections have high resistance and heat up as
- Compare ΔT with similar components at similar load, following NETA: 1–3 °C investigate, 4–15 °C repair as planned, over 15 °C repair immediately
- ΔT depends on load; estimate full load roughly with , and image at high load
- Image in light wind, avoid reflections, make connections span several pixels, and pair with zoom images
Check your understanding
- A connection reads 52 °C while the other phase at equal load reads 40 °C. Which NETA group is it in?
- A ΔT of 4 °C at 50% load estimates to what at full load?
- Why compare with other phases instead of using absolute temperature?
- How does strong wind affect measured ΔT?
- Why does a connection spanning only one thermal pixel read low?
Answers
- ΔT = 12 °C, in the 4–15 °C group: probable deficiency, repair as time permits
- °C
- Errors from emissivity, distance and wind affect all phases similarly, so comparison cancels them
- Wind carries heat away, so measured ΔT is lower than the truth
- That pixel’s temperature is averaged with the cooler background
Key formulas
| Temperature difference | |
| Resistive heating | |
| Estimated full-load ΔT |
Key references
- InterNational Electrical Testing Association. (2003). ANSI/NETA ATS-2003 Standard for acceptance testing specifications for electrical power equipment and systems (Table 100.18, Thermographic survey suggested actions based on temperature rise). link
- Vollmer, M., & Möllmann, K.-P. (2017). Infrared thermal imaging: Fundamentals, research and applications (2nd ed.). Wiley-VCH. link
- Teledyne FLIR. Comparing sensitivity of thermal imaging cameras and modules (NETD). link
- Teledyne FLIR. How does emissivity affect thermal imaging? link
Further reading
Study the assigned knowledge units in advance, review media and take the module quiz
In class / field
Lab or field practice from worksheets with a safety checklist
Learning evidence: Checked worksheets and quiz results