Module 8/15 · Weeks 8 · 9 h

Power lines and electrical connections

UAT 453 UAS for Infrastructure, Energy and Utility Inspection

About 80 minDraft, awaiting reviewLast updated 30 September 2026

Lesson

By the end of this module you will be able to

  1. Explain why electrical connections overheat and the principle of comparing with similar components
  2. Rate hot spots by severity using the NETA ΔT criteria
  3. Estimate full-load ΔT from a low-load measurement and explain its limits
  4. Define suitable conditions for thermal imaging of electrical systems

Prerequisites: Module 7 Sensor selection and route planning

Why this matters

A loose, dirty or corroded connection has higher resistance than normal. When current flows, heating concentrates there. Left alone, the connection gets hotter until the material degrades and breaks, causing an outage. Drone thermal imaging finds these spots without switching off power, but deciding which must be repaired immediately needs clear criteria and an understanding of electrical load.

Comparing with similar components

Temperatures read from a drone carry errors from emissivity, distance and wind, so absolute values are not very reliable. The widely used approach is to compare with similar components under similar load, such as the same type of connection on another phase of the same tower. The difference cancels errors that affect all phases alike.

Table 100.18 of ANSI/NETA ATS gives guidance by between similar components:

between similar componentsMeaning and action
1–3 °CPossible deficiency; warrants investigation
4–15 °CProbable deficiency; repair as time permits
Over 15 °CMajor discrepancy; repair immediately

The same table warns that temperature criteria vary by equipment type, and that heating relates to the square of current, so load at the time of measurement matters greatly.

Example 1 Rating four connections

readings = {   # connector: (measured °C, other phase at equal load °C)
    "tower 17 clamp phase A": (41.0, 38.5),
    "tower 17 clamp phase B": (38.5, 38.5),
    "tower 23 jumper phase C": (47.0, 38.0),
    "tower 31 clamp phase A": (61.0, 39.0),
}


def action(dt):
    if dt > 15:
        return "major discrepancy, repair immediately"
    if dt >= 4:
        return "probable deficiency, repair as time permits"
    if dt >= 1:
        return "possible deficiency, investigate"
    return "no action"


for name, (t, ref) in readings.items():
    print(f"{name:<24} dT {t - ref:4.1f} C -> {action(t - ref)}")
tower 17 clamp phase A   dT  2.5 C -> possible deficiency, investigate
tower 17 clamp phase B   dT  0.0 C -> no action
tower 23 jumper phase C  dT  9.0 C -> probable deficiency, repair as time permits
tower 31 clamp phase A   dT 22.0 C -> major discrepancy, repair immediately

The connection at tower 31 is 22 °C hotter than the other phase, a major discrepancy needing immediate repair. Tower 23 differs by 9 °C, to be repaired as planned. Tower 17 phase A differs by 2.5 °C and should be re-checked or imaged from another angle, because such a small difference may come from camera angle, sunlight or slight emissivity differences.

Horizontal bar chart of ΔT for four connections: tower 17 phase A 2.5 degrees in blue, tower 17 phase B 0 degrees, tower 23 phase C 9 degrees in yellow, tower 31 phase A 22 degrees in pink. Dashed purple lines mark the 1, 4 and 15 degree criteria
Figure 1 Connector ΔT against the 1, 4 and 15 °C criteria

The effect of electrical load

Because heating scales with , a faulty connection may not look very hot when measured at low load. A simple estimate of full-load ΔT multiplies by the square of the current ratio

Example 2 Measured at 40% load

DT_MEASURED, LOAD_NOW, LOAD_FULL = 6.0, 0.40, 1.00   # measured ΔT, and load fraction now versus full
dt_full = DT_MEASURED * (LOAD_FULL / LOAD_NOW) ** 2  # heating scales with current squared (approximation)
print(f"measured {DT_MEASURED} C at {LOAD_NOW:.0%} load -> about {dt_full:.1f} C at full load")
measured 6.0 C at 40% load -> about 37.5 C at full load

A ΔT of 6 °C at 40% load appears to be in the “repair as time permits” group, but at full load it could reach about 37.5 °C, far above the major threshold. This simple estimate ignores cooling that changes with temperature and wind; use it as a warning to prioritise, not as an exact reported figure. Better practice is to schedule imaging at high load, using load data from the control centre.

Two bars: ΔT measured at 40 percent load, 6 degrees in yellow, and estimated at full load, 37.5 degrees in pink, with a dashed purple line at 15 degrees
Figure 2 ΔT measured at low load versus full load

Suitable conditions for electrical thermography

  • High enough load, per the owner’s data, recording the load at every measurement
  • Light wind, because wind carries heat away and lowers ΔT
  • Avoid strong direct sun and reflections: shiny metal reflects radiation from the sky and sun, so early morning or after sunset often gives easier interpretation
  • Enough distance and pixels: connections must span several thermal pixels, or their temperature is averaged with the background and reads low
  • Paired zoom RGB images to identify which part the hot spot is

Module lab

Lab: thermal images of an electrical panel

  1. Under the supervision of the university’s electrical staff, take thermal images of a control panel or connections that can be reached safely (a handheld or ground-based thermal camera is fine)
  2. Read the temperature of the same type of connection on every phase, compute ΔT and rate it with the code in Example 1
  3. Obtain the load at the time of measurement and estimate full-load ΔT with the code in Example 2
  4. Record wind, light and time, and write how these conditions might bias the results

Common mistakes

Watch out

  • Judging by absolute temperatures from the drone instead of comparing with similar components
  • Not recording load at measurement, so ΔT cannot be interpreted
  • Imaging in strong wind or direct sun, then concluding there are no hot spots
  • Imaging from so far that connections span only a few pixels, so temperatures are averaged low
  • Reporting estimated full-load ΔT as an exact figure

Summary

  • Faulty connections have high resistance and heat up as
  • Compare ΔT with similar components at similar load, following NETA: 1–3 °C investigate, 4–15 °C repair as planned, over 15 °C repair immediately
  • ΔT depends on load; estimate full load roughly with , and image at high load
  • Image in light wind, avoid reflections, make connections span several pixels, and pair with zoom images

Check your understanding

  1. A connection reads 52 °C while the other phase at equal load reads 40 °C. Which NETA group is it in?
  2. A ΔT of 4 °C at 50% load estimates to what at full load?
  3. Why compare with other phases instead of using absolute temperature?
  4. How does strong wind affect measured ΔT?
  5. Why does a connection spanning only one thermal pixel read low?
Answers
  1. ΔT = 12 °C, in the 4–15 °C group: probable deficiency, repair as time permits
  2. °C
  3. Errors from emissivity, distance and wind affect all phases similarly, so comparison cancels them
  4. Wind carries heat away, so measured ΔT is lower than the truth
  5. That pixel’s temperature is averaged with the cooler background

Key formulas

Temperature difference
Resistive heating
Estimated full-load ΔT

Key references

  1. InterNational Electrical Testing Association. (2003). ANSI/NETA ATS-2003 Standard for acceptance testing specifications for electrical power equipment and systems (Table 100.18, Thermographic survey suggested actions based on temperature rise). link
  2. Vollmer, M., & Möllmann, K.-P. (2017). Infrared thermal imaging: Fundamentals, research and applications (2nd ed.). Wiley-VCH. link
  3. Teledyne FLIR. Comparing sensitivity of thermal imaging cameras and modules (NETD). link
  4. Teledyne FLIR. How does emissivity affect thermal imaging? link

Further reading

Study the assigned knowledge units in advance, review media and take the module quiz

In class / field

Lab or field practice from worksheets with a safety checklist

Learning evidence: Checked worksheets and quiz results

Module quiz