UAT 453 UAS for Infrastructure, Energy and Utility Inspection
Worksheet 8 Thermal images of an electrical panel
Objective
Safely thermally image electrical connections, rate them by ΔT, scale to full load and assess environmental effects on the readings
Equipment and materials
- Handheld or ground-based thermal camera
- Load data at measurement time from staff
- Anemometer
- Computer with Python and the module 8 example code
Safety
- Work only under the university electrical staff's supervision
- Image from the distance staff set; never touch or open panels yourself
- Use ground-based cameras; no drone flights near electrical equipment
Steps
- Thermally image a panel or safely reachable connections
- Read the temperature of the same connection type on every phase
- Compute ΔT and rate with Example 1
- Obtain the load and estimate full-load ΔT with Example 2
- Record wind, light and time and explain how they might bias results
Record of results
| Connection and phase (image no.) | Temperature (°C) | Reference phase (°C) | ΔT (°C) | NETA group |
|---|---|---|---|---|
| Connection | Load at measurement (%) | Measured ΔT (°C) | Estimated full-load ΔT (°C) | Group at full load |
|---|---|---|---|---|
| Condition | Recorded value | Makes ΔT read high or low | Reason |
|---|---|---|---|
Questions
Which NETA group is your highest-ΔT connection in, and what should happen next?
Did the full-load estimate move any connection to another group? Why should it not be reported as an exact figure?
Why compare with other phases instead of absolute temperature? Use your data.
Which way did wind and sun during your measurement likely bias the result, and under what conditions should you re-measure?
Check before you hand in
What to hand in
- Thermal images labelled by location and phase
- Ratings at actual and full load
- Environmental notes and their effect on error