Module 10/10 · Weeks 15 · 14 h

Data analytics and security of smart warehouse systems

UAT 459 UAS, Internet of Things and Smart Warehouse Systems

About 100 minDraft, awaiting reviewLast updated 24 October 2026

Lesson

By the end of this module you will be able to

  1. Calculate mean kinetic temperature (MKT) and explain how it summarises thermal stress and where it falls short
  2. Analyse drone vertical temperature profiles to find stratification and hot spots in a high-bay hall
  3. Use an EWMA control chart to detect slow equipment changes for maintenance before failure
  4. Assess system security with IEC 62443 zones and conduits, and use ETSI EN 303 645, NIST IR 8259A and Thai law as criteria for procurement and operation
  5. Choose charts that answer the reader's question and build a status board that shows limits, extremes and missing data instead of means alone

Prerequisites: Modules 6 to 9 · UAT 207 Communication and Data Network Systems (recommended)

Why this matters

The distribution centre stores over 130,000 temperature values a day. They are worth something only if they help decisions: is the vaccine that went through a six-hour refrigeration fault still usable, is the top of the high-bay hall too hot in the hot season, which compressor is about to fail? At the same time, a system that decides such important matters becomes a target. An attacker who can forge temperature readings can hide an excursion until degraded medicine reaches patients, or demand a ransom by locking the whole platform.

This final module covers the last two topics of the course description: data analytics and security of smart warehouse systems.

Mean kinetic temperature

When a cold room leaves its range for six hours, the weekly average may still look normal. But drug degradation reactions speed up exponentially with temperature, following the Arrhenius equation, so hot periods weigh more than their share of time. ICH Q1A(R2) defines mean kinetic temperature (MKT) as a single derived temperature that, if maintained over a defined period, gives the same thermal challenge to a product as the actual varying temperatures. MKT is always higher than the arithmetic mean and is calculated with the Haynes formula (International Conference on Harmonisation, 2003; Haynes, 1971). ICH is merging Q1A to Q1E into a single Q1 guideline (draft endorsed in April 2025, final adoption planned for November 2026), and Q1A(R2) stays in force until then, so check the version in force.

where are temperatures in kelvin over equal periods and is the activation energy. Tong and Lock (2015) explain that the United States Pharmacopeia (USP) adopted a default of 83.144 kJ/mol unless better experimental data exist, which gives exactly K, and they present a formula for unequally spaced data, such as from loggers that record more often during an alarm. WHO Supplement 6 lists MKT reports among the outputs a monitoring system should provide (World Health Organization, 2015a).

Example 1 MKT of a week with a six-hour refrigeration fault

Hourly cold-room temperatures over one week swing around 5 °C, with a six-hour fault on day five peaking at 13.5 °C (simulated data).

import math
# mean kinetic temperature (Haynes formula) of one week of hourly readings in the cold room (assumed)
EA_R = 10000.0                         # Ea / R in kelvin, from the default Ea of 83.144 kJ/mol
temps = [5.0 + 0.4 * math.sin(2 * math.pi * h / 24) for h in range(168)]
for h in range(100, 106):              # 6-hour refrigeration fault on day 5
    temps[h] = [9.0, 11.5, 13.0, 13.5, 12.0, 9.5][h - 100]
def mkt(values_c):
    s = sum(math.exp(-EA_R / (t + 273.15)) for t in values_c) / len(values_c)
    return EA_R / -math.log(s) - 273.15
mean = sum(temps) / len(temps)
print(f"arithmetic mean {mean:.2f} °C, MKT {mkt(temps):.2f} °C, max {max(temps):.1f} °C")
print(f"hours above 8 °C: {sum(t > 8 for t in temps)}")
print(f"same week without the fault: MKT {mkt([5.0 + 0.4 * math.sin(2 * math.pi * h / 24) for h in range(168)]):.2f} °C")
arithmetic mean 5.22 °C, MKT 5.34 °C, max 13.5 °C
hours above 8 °C: 6
same week without the fault: MKT 5.00 °C

The fault raises MKT from 5.00 to 5.34 °C, more than the 0.22 °C rise in the arithmetic mean, showing that hot periods weigh more than their time. The key caution is that the weekly MKT is still within 2 to 8 °C even though the product reached 13.5 °C. MKT is therefore not evidence that the product is safe. Some products, such as vaccines and biologics, may be harmed more by peak temperature or freezing than by total thermal load. QA must assess the peak, the duration and the product’s stability data; MKT is only one input.

Line chart of hourly temperature over one week, 0 to 168 hours on the horizontal axis and 2 to 14 degrees on the vertical. The blue line swings slightly around 5 degrees with a peak of 13.5 degrees around hours 100 to 105. A pink dashed line marks 8.0 degrees. A green line at the mean of 5.22 and a purple dashed line at the MKT of 5.34 lie very close together
Figure 1 Hourly temperature over one week, its mean and MKT

Vertical temperature profiles by drone

WHO Supplement 8 on temperature mapping (World Health Organization, 2015b) warns that high-bay racking stores are prone to temperature stratification: hot air rises and accumulates at the top, so the store must be mapped over its full working height. The supplement places loggers on a grid every 5 to 10 metres across width and length, with vertical arrays at each grid point, for example at 0.3, 1.8, 3.6 and 5.4 m in a 6 m room, logging every 1 to 15 minutes, and for ordinary warehouses running at least seven consecutive days including a weekend. Hot and cold spots found this way decide where permanent monitoring sensors go, and must be checked seasonally because summer and winter differ.

A drone does not replace a seven-day mapping study, but it fills the gap between studies: a vertical profile at any point in a single night, for example after a racking layout change or when fixed sensors suggest the upper levels are unusually warm. A caution: rotor wash mixes the air around the drone, so the probe must sit on a boom away from the body, respond quickly, and be allowed to settle at each level. If the probe has time constant , waiting brings the reading to of a step change.

Example 2 Drone profiles at three rack columns in hall Z1

A drone measures three rack columns in the 15 to 25 °C hall on a hot afternoon, six levels each. The probe’s time constant is 8 seconds and moving between points takes 10 seconds (assumed values).

# vertical profiles in the 15-25 °C high-bay hall from a drone-carried probe at three rack columns (assumed)
heights = [0.3, 1.8, 3.6, 5.4, 7.2, 8.7]
profiles = {"C05 near dock": [19.6, 20.1, 21.0, 22.4, 23.9, 25.3],
            "C18 centre":    [19.2, 19.5, 20.1, 20.9, 21.8, 22.6],
            "C31 back wall": [18.8, 19.0, 19.4, 20.0, 20.7, 21.3]}
for col, t in profiles.items():
    grad = (t[-1] - t[0]) / (heights[-1] - heights[0])
    over = [h for h, v in zip(heights, t) if v > 25.0]
    print(f"{col:<14} top-bottom {t[-1] - t[0]:.1f} °C ({grad:.2f} °C/m), above 25 °C at {over} m")
TAU, POINTS, MOVE_S = 8, 3 * len(heights), 10      # probe time constant s, hover points, s between points
hover_s = 5 * TAU                                   # wait 5 time constants: 99.3 % of a step change
print(f"settling after a step: {1 - math.exp(-5):.1%}; flight time {(POINTS * (hover_s + MOVE_S)) / 60:.1f} min")
C05 near dock  top-bottom 5.7 °C (0.68 °C/m), above 25 °C at [8.7] m
C18 centre     top-bottom 3.4 °C (0.40 °C/m), above 25 °C at [] m
C31 back wall  top-bottom 2.5 °C (0.30 °C/m), above 25 °C at [] m
settling after a step: 99.3%; flight time 15.0 min

Column C05 near the dock is hottest and exceeds 25 °C at the top level, 8.7 m. A 5.7 °C top-to-bottom difference shows clear stratification. The recommendation is to stop storing product on the top level of the columns near the dock until air distribution is adjusted, then re-map to confirm, following the WHO procedure. The whole flight takes 15 minutes, within the battery endurance of a typical indoor drone, but the result is a single snapshot; deciding which areas may hold product still requires continuous mapping.

Vertical temperature profiles with temperature 18 to 26 degrees on the horizontal axis and height 0 to 9 metres on the vertical. Three lines: C05 in pink from 19.6 degrees at 0.3 metres to 25.3 degrees at 8.7 metres, C18 in yellow from 19.2 to 22.6 degrees, and C31 in blue from 18.8 to 21.3 degrees. A vertical pink dashed line marks 25 degrees, and only the top point of C05 lies to its right
Figure 2 Drone vertical temperature profiles at three rack columns

Maintenance before failure with an EWMA chart

Refrigeration rarely fails at once. A fouled condenser or a slow refrigerant leak makes the compressor run a little longer each day for weeks before it can no longer keep up. The daily compressor duty cycle from the PLC is therefore a good early warning, but small changes are buried in day-to-day variation.

The NIST statistics handbook describes the EWMA (exponentially weighted moving average) control chart, which averages data with ever-decreasing weights on older values, , making it more sensitive to slow drift than a chart of single values. is usually set between 0.2 and 0.3 and the control limits are , with commonly 3 (NIST/SEMATECH, n.d.).

Example 3 Detecting drift in compressor duty cycle

In the first month after commissioning the duty cycle averaged 42% with a standard deviation of 1.5%. From day 19 the condenser starts to foul and the value rises by about 0.6% a day (simulated data).

# EWMA chart on the daily compressor duty cycle of the cold room (simulated, %)
base = [42.0, 44.1, 40.3, 43.5, 41.2, 39.8, 42.7, 44.0, 41.5, 40.9, 43.1, 42.2, 40.4, 41.8, 43.3,
        42.5, 41.0, 43.8]
drift = [42.0 + 0.6 * d + x for d, x in enumerate([1.1, -0.6, 0.9, -1.4, 0.3, 1.2, -0.2, 0.8, -0.9,
                                                       0.5, 1.0, -0.3])]
duty = base + drift                                  # a slow rise starts on day 19 (fouled condenser)
MU, S, LAM, K = 42.0, 1.5, 0.2, 3                    # target and sd from the commissioning month
lim = K * S * math.sqrt(LAM / (2 - LAM))
ewma, first_e, first_s = MU, None, None
for day, y in enumerate(duty, start=1):
    ewma = LAM * y + (1 - LAM) * ewma
    if first_e is None and ewma > MU + lim:
        first_e = day
    if first_s is None and y > MU + K * S:
        first_s = day
print(f"EWMA limit {MU + lim:.2f} %, single-value limit {MU + K * S:.2f} %")
print(f"EWMA signals on day {first_e}, single-value chart on day {first_s}")
EWMA limit 43.50 %, single-value limit 46.50 %
EWMA signals on day 24, single-value chart on day 26

EWMA signals on day 24, two days before the single-value chart, and both warn before the cold room starts to warm. Technicians can clean the condenser on schedule instead of making an emergency repair at two in the morning. The target and standard deviation must come from a period when the system was truly normal, and must be reset as seasons change, because duty cycle is naturally higher in the hot season.

Showing the results: charts that lead to a decision

The analysis of this module reaches people through screens: the QA manager, the technician on duty, the warehouse supervisor. A dashboard that hides the answer is as useless as no analysis at all. Four rules help.

  1. Fit the chart to the question. Grafana’s guidance is to keep a graph simple and focused on the question being asked; if the question is “which servers are in trouble?”, show only the ones in trouble (Grafana Labs, n.d.). For a cold room, a line with the limits drawn on it answers “is it in range?”, a heat map of column against level answers “where is it hot?”, and a list sorted worst-first answers “what needs me now?”.
  2. Use the visual tasks people judge best. Cleveland and McGill (1984) ordered elementary visual tasks by how accurately people perform them and advised building graphs from tasks as high in the order as possible; they concluded that popular pie charts and shaded maps need “radical surgery” and proposed dot charts instead. Use a heat map to find where, then read exact values from a table or dot chart.
  3. Show the limit and the extremes. A mean hides an excursion (Figure 1 above: a mean of 5.22 °C against a peak of 13.5 °C), so draw the limits and show the minimum and maximum.
  4. Never rely on colour alone, and never let silence look like health. WCAG success criterion 1.4.1 says colour must not be the only visual means of conveying information (World Wide Web Consortium, n.d.), so every state needs a word or a shape. A sensor that has stopped reporting must show NO DATA, not its last value or a green tile.

Example 4 A status board that cannot be fooled by a mean

Six sensors, last 180 minutes, one reading a minute (simulated, seed fixed). T1-02 had a door open for 6 minutes; T1-03 has a refrigeration fault for the last 40 minutes; T1-04 stopped reporting after 60 minutes; T1-05 loses about a quarter of its readings; T1-06 creeps upward. The rules are assumed: NO DATA if the newest reading is over 10 minutes old; ALARM if the last 15 readings are all above 8.0 °C (the delayed alarm of module 9); WARN if any reading passed the 7.6 °C pre-alarm level or fewer than 90% of the readings arrived; otherwise ok. The board is sorted worst-first and each row also shows the mean, as a tile would.

import random
# status board for six cold-room sensors from the last 180 minutes (simulated, seed fixed); one reading per minute
rng = random.Random(459)
def series(base, spike=None, hot_from=None, dead_from=None, miss=0.0, creep=0.0):
    out = {}                                                   # minute -> reading; a missing minute has no entry
    for m in range(180):
        if (dead_from is not None and m >= dead_from) or rng.random() < miss:
            continue
        v = base + creep * m + rng.gauss(0, 0.15)
        if spike and spike[0] <= m < spike[1]:
            v = 8.6                                            # door open
        if hot_from is not None and m >= hot_from:
            v = 8.4 + rng.gauss(0, 0.1)                        # refrigeration fault
        out[m] = v
    return out
sensors = {"T1-01": series(5.2), "T1-02": series(5.0, spike=(100, 106)), "T1-03": series(5.1, hot_from=140),
           "T1-04": series(5.3, dead_from=60), "T1-05": series(5.2, miss=0.25), "T1-06": series(5.0, creep=0.0145)}
def status(r):
    last = max(r)
    if 179 - last > 10:
        return 3, "NO DATA", f"last reading {179 - last} min ago"
    if all(r.get(m, 0) > 8.0 for m in range(165, 180)):
        return 4, "ALARM", "above 8.0 C for 15 min"
    if max(r.values()) > 7.6:
        return 2, "WARN", f"peak {max(r.values()):.1f} C above the 7.6 C pre-alarm level"
    if len(r) < 0.9 * 180:
        return 2, "WARN", f"only {len(r)} of 180 readings"
    return 0, "ok", "within limits"
for name, r in sorted(sensors.items(), key=lambda kv: -status(kv[1])[0]):
    mean = sum(r.values()) / len(r)
    _, label, why = status(r)
    print(f"{label:8s} {name}  mean {mean:.1f} C  {why}")
ALARM    T1-03  mean 5.8 C  above 8.0 C for 15 min
NO DATA  T1-04  mean 5.3 C  last reading 120 min ago
WARN     T1-02  mean 5.1 C  peak 8.6 C above the 7.6 C pre-alarm level
WARN     T1-05  mean 5.2 C  only 129 of 180 readings
WARN     T1-06  mean 6.3 C  peak 8.0 C above the 7.6 C pre-alarm level
ok       T1-01  mean 5.2 C  within limits

Every mean lies between 5.1 and 6.3 °C, so a board of mean tiles would show six healthy sensors. The status board finds the real alarm (T1-03, whose mean is only 5.8 °C because the fault covers 40 of the 180 minutes), a dead sensor whose old readings would have looked fine for two hours, a door opening that needs no action, a sensor that loses about a quarter of its readings and one that is creeping towards the limit. Every state is a word, so it survives a black-and-white printout and a colour-blind reader; colour can be added on top. Ranking NO DATA above WARN is a design choice: a silent sensor protects nothing.

Security with zones and conduits

A smart warehouse mixes information technology (IT) with operational technology (OT) that controls real equipment. The IEC explains that IT standards alone do not suit industrial automation and control systems (IACS), which have different performance and availability requirements and equipment lifetimes, and where attacks can affect health and lives. The IEC 62443 series therefore takes a risk-based approach rather than protecting all assets equally, and covers technology, processes and people (International Electrotechnical Commission, 2021).

Key concepts from the ISA Global Cybersecurity Alliance overview (2023):

  • A zone is a grouping of logical or physical assets with common security requirements; a conduit is a grouping of communication channels between zones that share common security requirements. Part 3-2 calls for wireless devices, temporarily connected devices and devices connected through external networks to be partitioned into their own zones
  • Seven foundational requirements (FR): FR1 identification and authentication control, FR2 use control, FR3 system integrity, FR4 data confidentiality, FR5 restricted data flow, FR6 timely response to events and FR7 resource availability
  • Security levels (SL): SL 1 protects against casual or coincidental violation; SL 2 against intentional violation with simple means, low resources and generic skills; SL 3 against sophisticated means, moderate resources and IACS-specific skills; SL 4 against attackers with extended resources and high motivation
  • SL-T is the target level from risk assessment, SL-C the capability a system or component offers when properly configured, and SL-A the level actually achieved after installation
Five zones. A yellow enterprise box with WMS and ERP at the top, SL-T 2, connects through conduit C1 down to a purple IoT platform box in the centre, SL-T 2. From the platform, conduit C2 goes to a blue refrigeration PLC box at lower left, SL-T 3, C3 goes to a green box of wireless sensors and gateways at lower centre, SL-T 2, and C4 goes to an orange drones and docks box at lower right, SL-T 2
Figure 3 Zones and conduits of the system after IEC 62443

The team divides the system into five zones as in Figure 3. The refrigeration PLCs get SL-T 3, because an attacker controlling them could switch off cooling for a room full of vaccine; the other zones get SL-T 2. All traffic between zones must pass through defined conduits; for example, C2 allows the platform only to read values and send the standby switchover command over authenticated OPC UA, and there is no path from the office network straight to the PLCs.

Example 5 Finding gaps between SL-T and SL-C by FR

The team rates the target level and the device capability of each zone for FR1 to FR7 from vendor documents and testing (assumed assessment).

# target (SL-T) and capability (SL-C) per foundational requirement FR1-FR7 for each zone (team assessment, assumed)
zones = {"Wireless sensors": ([2, 2, 2, 1, 2, 1, 2], [1, 1, 2, 1, 1, 1, 1]),
         "Refrigeration PLCs": ([3, 3, 3, 1, 3, 2, 3], [2, 2, 2, 1, 2, 2, 2]),
         "IoT platform": ([2, 2, 2, 2, 2, 2, 2], [3, 3, 2, 3, 2, 2, 2]),
         "Drones and docks": ([2, 2, 2, 2, 2, 1, 2], [2, 1, 2, 2, 2, 1, 1])}
for zone, (target, cap) in zones.items():
    gaps = [f"FR{i + 1}" for i, (t, c) in enumerate(zip(target, cap)) if c < t]
    print(f"{zone:<19} gaps: {', '.join(gaps) if gaps else 'none'}")
Wireless sensors    gaps: FR1, FR2, FR5, FR7
Refrigeration PLCs  gaps: FR1, FR2, FR3, FR5, FR7
IoT platform        gaps: none
Drones and docks    gaps: FR2, FR7

Cheap wireless sensors authenticate weakly (FR1) and nothing restricts who may inject data (FR5). If a fake sensor sends 5 °C over the real reading, the system will not see an excursion. This gap is closed by compensating countermeasures at the zone or conduit, such as gateways that accept only registered sensors with individual keys, plausibility checks (module 7) and comparison with neighbouring sensors. The legacy PLCs have the most gaps, so they sit behind an industrial firewall that allows only defined OPC UA commands, with replacement considered in the next investment cycle. The platform shows no gaps, but its SL-A must still be proven after installation and configuration.

Procurement criteria and relevant law

Most gaps in Example 5 are created on the day devices are bought, so good procurement criteria prevent them more cheaply than later fixes. Two documents serve as a base.

  • ETSI EN 303 645 V3.1.3 (ETSI, 2024), baseline security requirements for consumer IoT, has thirteen sections: no universal default passwords, a way to manage vulnerability reports, keep software updated, securely store sensitive security parameters, communicate securely, minimise exposed attack surfaces, ensure software integrity, ensure personal data is secure, make systems resilient to outages, examine system telemetry, make it easy to delete user data, make installation and maintenance easy, and validate input data. Although written for consumer devices, low-cost warehouse sensors and gateways often share the same hardware and software class, so it makes a suitable minimum
  • NIST IR 8259A (Fagan et al., 2020) sets six core device capabilities: device identification, device configuration, data protection, logical access to interfaces, software update and cybersecurity state awareness

On the legal side, location data from forklift tags and camera images from drones flying in the racking hall may identify staff, so they are personal data under the Personal Data Protection Act B.E. 2562 (2019) (Personal Data Protection Act B.E. 2562, 2019), requiring a stated purpose, minimal collection and a retention period. In addition, the Cybersecurity Act B.E. 2562 (2019) (Cybersecurity Act B.E. 2562, 2019) places extra duties on critical information infrastructure organisations. The company should check whether it, or customers such as hospitals, fall within that scope, since requirements may be passed down to suppliers.

Module lab

Lab: a data analysis and security assessment report on the mock system

  1. Using at least one week of data accumulated by the mock system of modules 7 to 9 (or simulated data from the instructor), calculate MKT as in Example 1 for a normal period and a period with a simulated event, and write one paragraph for QA stating MKT, peak temperature and duration
  2. If an indoor drone and an authorised space are available, fly vertical profiles at two columns with a probe on a boom under instructor supervision (or use a pole that raises the probe level by level instead), and analyse as in Example 2
  3. Simulate 30 days of duty cycle with a drift and compare EWMA at of 0.1, 0.2 and 0.3 as in Example 3
  4. Divide the group’s mock system into zones and conduits, set SL-T per FR with reasons, rate SL-C from the documents of the actual devices used, find gaps as in Example 5 and propose compensating countermeasures, then check one device against the sections of ETSI EN 303 645

Common mistakes

Watch out

  • Treating an in-range MKT as proof the product is safe, without looking at peak, duration and stability data
  • Using a single drone profile instead of temperature mapping, or measuring with the probe in rotor wash
  • Setting the EWMA target from a period when the equipment was already failing, or not adjusting for seasons
  • Protecting everything equally instead of zoning by risk, and letting the office network reach the PLCs directly
  • Buying devices first and thinking about security later, when most gaps are cheapest to close at procurement
  • A dashboard of mean tiles, which shows a healthy room while the fault lasts a quarter of the day or a sensor has gone silent

Summary

  • MKT by the Haynes formula, with K as default, summarises thermal stress better than the mean but does not replace assessing peak and duration
  • High-bay stores are prone to stratification; drone vertical profiles complement WHO mapping if the probe settles for and avoids rotor wash
  • EWMA catches slow drift earlier than single values, supporting maintenance before failure
  • IEC 62443 divides the system into zones and conduits, sets SL-T per FR and closes gaps with SL-C through compensating countermeasures; ETSI EN 303 645 and NIST IR 8259A serve as procurement criteria, and PDPA applies whenever data identify staff
  • Show results so that people can decide: fit the chart to the question, show limits and extremes, never rely on colour alone, and let a silent sensor show NO DATA rather than a healthy tile

Check your understanding

  1. Four equal periods are at 5, 5, 5 and 15 °C. What are the arithmetic mean and the MKT ( K)?
  2. Why is an MKT within 2 to 8 °C not enough to conclude that a vaccine is usable?
  3. A probe has a time constant of 12 seconds. How long must it wait at each level to reach 99.3% of a step change?
  4. An EWMA uses , and a standard deviation of 2.0%. How far are the limits from the target?
  5. A zone has SL-T 3 for FR1 but its devices offer SL-C 2. What should the team do?
Answers
  1. The mean is °C; MKT works out at about 8.8 °C, higher than the mean because the 15 °C period carries exponential weight
  2. MKT summarises total thermal load but hides peak temperature and time out of range; some vaccines are harmed by peaks or freezing, so QA must assess against the product’s stability data
  3. seconds
  4. % above and below the target
  5. Apply compensating countermeasures at the zone or conduit, such as a firewall allowing only defined commands and authentication at the gateway or access point, record the residual risk, and plan to replace devices with ones offering SL-C 3 in the next cycle

Key formulas

Mean kinetic temperature (Haynes formula)
EWMA statistic
EWMA control limits
Security level gap

Key references

  1. International Conference on Harmonisation. (2003). Stability testing of new drug substances and products Q1A(R2) (ICH harmonised tripartite guideline). link
  2. Haynes, J. D. (1971). Worldwide virtual temperatures for product stability testing. Journal of Pharmaceutical Sciences, 60(6), 927–929. link
  3. Tong, C., & Lock, A. (2015). A computational procedure for mean kinetic temperature using unequally spaced data. In JSM Proceedings, Biopharmaceutical Section (pp. 2065–2070). American Statistical Association. link
  4. World Health Organization. (2015). Temperature and humidity monitoring systems for fixed storage areas: Technical supplement to WHO Technical Report Series, No. 961, 2011, Annex 9 (Supplement 6). WHO. link
  5. World Health Organization. (2015). Temperature mapping of storage areas: Technical supplement to WHO Technical Report Series, No. 961, 2011, Annex 9 (Supplement 8). WHO. link
  6. NIST/SEMATECH. EWMA control charts (section 6.3.2.4). e-Handbook of statistical methods. National Institute of Standards and Technology. link
  7. International Electrotechnical Commission. (2021, February 26). Understanding IEC 62443. IEC. link
  8. ISA Global Cybersecurity Alliance. (2023). Security of industrial automation and control systems: An overview of ISA/IEC 62443 standards. International Society of Automation. link
  9. ETSI. (2024). Cyber security for consumer Internet of Things: Baseline requirements (ETSI EN 303 645 V3.1.3). link
  10. Fagan, M., Megas, K. N., Scarfone, K., & Smith, M. (2020). IoT device cybersecurity capability core baseline (NISTIR 8259A). National Institute of Standards and Technology. link
  11. พระราชบัญญัติคุ้มครองข้อมูลส่วนบุคคล พ.ศ. 2562. ราชกิจจานุเบกษา, 136(69 ก), 52–95. link
  12. พระราชบัญญัติการรักษาความมั่นคงปลอดภัยไซเบอร์ พ.ศ. 2562. (2562). ราชกิจจานุเบกษา, 136(69 ก). link
  13. Cleveland, W. S., & McGill, R. (1984). Graphical perception: Theory, experimentation, and application to the development of graphical methods. Journal of the American Statistical Association, 79(387), 531-554. link
  14. Grafana Labs. (n.d.). Grafana dashboard best practices. Grafana documentation. link
  15. World Wide Web Consortium. (n.d.). Understanding success criterion 1.4.1: Use of color (WCAG 2.2). W3C Web Accessibility Initiative. link

Further reading

Study the assigned knowledge units in advance, review media and take the module quiz

In class / field

Lab or field practice from worksheets with a safety checklist

Learning evidence: Checked worksheets and quiz results

Module quiz

This is a formative self-check, not a graded exam

Knowledge domain: Mathematics, physics and statistics · Programming and digital technology · Cybersecurity and UAS traffic management · Law, safety and risk · Management, innovation and professional practice